Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM02923
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM02923 3422 S Nayasa Ave - R-1 Room Addition & Enclose Porch (1st Review) TRANSMITTAL: April 21, 2022 This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9. The provided plot plan does not match the parcel at 3422 S Nayasa Ave. Appears to be for 7902 S New Abbey Dr. Provide a plot plan for the correct address. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 04/21/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 04/21/2022 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 05/04/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T22CM02923 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans. Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. FLOOR PLANS: 1. Show the functional name of each proposed room and each adjacent room, R106.1.1. Existing bedrooms with removed or enclosed windows must show code compliance for egress, R310. SECTIONS - DETAILS: 1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. MECHANICAL PLANS: 1. Provide heating facilities in all habitable rooms, R303.9. 2. Show the existing bathroom (without a window) exhaust fan locations with minimum 50 CFM rating and duct to the exterior, R303.3 and M1505. ELECTRICAL PLANS: 1. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.2.2. Provide notation if the smoke alarms are existing or proposed. 2. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6. 3. Protect extended branch circuits with combination type arc-fault circuit interrupters, or an AFCI type receptacle at the first outlet on the branch circuit, E3902.17. If you have any questions, please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |