Permit Number: T22CM02912
Parcel: 13605125A

Address:
9009 E 29th ST

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM02912
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2022 ARUIZ1 OIP REVIEW Completed
06/29/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02912

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Plans do not include wind uplift calculations. 2018 IRC - 301.1. Provide wind uplift calculations used and verify fastener type and location.
2. Plans do not include deadload calculations. 2018 IRC - 301.1. Provide structural calculations showing the existing roof system is capable of supporting the additional dead loads of the PV system.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
1. Grounding of PV fused disconnect required. 2017 NEC - 690.47(A), 250.142(A). Ground PV fused disconnect enclosure to grounding electrode system; not by bonding the EQG to the grounded conductor in the enclosure.


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2022 VVERA1 OUT TO CUSTOMER Completed