Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM02906
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2022 | PCAMARE1 | OIP | REVIEW | Approved | |
| 06/23/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM02906 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Incorrect windspeed used for design. 2018 IRC - Chapter 44. Revise structural calculations to show the correct Vult of 103mph was used. The calculations indicate that a 90mph Vult was used for wind design. The Vult from ASCE 7-16 is 103 mph; not 90 mph as shown in the structural calculations. 2. Missing information. The structural calculations do not clearly indicate the diameter of fasteners used, or the embedment depth into the supporting structural member. BUILDING REVIEW COMMENTS: Denied 1. Not able to read or open the .pdf plan file. Resubmit plans in a readable format so a review can be completed. MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Denied 1. Not able to read or open the .pdf plan file. Resubmit plans in a readable format so a review can be completed. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/23/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |