Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM02905
Parcel: 123141950

Address:
1940 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM02905
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM02521 - T22CM02905
Commercial Solar (1st Review)
1940 N 1ST AV Zoning R-3 /O-3
TRANSMITTAL DATE: ?April 20, ?2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



1. The proposed easement running across the alley will need to be recorded prior to approval of this plan. Provide copies of the recorded easement and provide the recordation information on the plan.


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
04/26/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/27/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/11/2022 JPEELDA1 FIRE REVIEW Reqs Change System is required to have rapid shutdown switches and signs. Provide diagram showing the location of the rapid shut down with the adjacent required sign per IFC 2018, 1204.5.1.2 & 1204.5.3
1820 N stone building exceeds 250 therefore a 6' path shall be provided at the permeter IFC 2018, 1204.3.1

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
05/24/2022 PCAMARE1 ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/24/2022 VVERA1 OUT TO CUSTOMER Completed