Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM02902
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/20/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
04/20/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
04/20/2022 | SSHIELD1 | NPPO | REVIEW | Passed | |
04/26/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans. Identify the function of the proposed room. A bedroom also requires a smoke alarm at the exterior side of door, R314.3.2. Show existing or altered conditioned air supply to the room, R303.9. Show the location of a light switch at the proposed door, R3903.3. Show if the window is existing or proposed. A bedroom requires a window opening with net clear 24" high opening, R310. |