Permit Number: T22CM02887
Parcel: 132191240

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM02887
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Replacement of an AC unit constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacity of the unit being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The unit will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizer. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/20/2022 NGARCIA3 OUT TO CUSTOMER Completed