Permit Number: T22CM02868
Parcel: 116183020

Address:
29 N MELROSE AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM02868
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2022 PAUL CAMARENA ZONING REVIEW Passed
04/20/2022 PCAMARE1 ENGINEERING REVIEW Passed
04/20/2022 PCAMARE1 NPPO REVIEW Passed
04/20/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a panel schedule with circuit sizes.

Show kitchen countertops with two 20 AMP circuits. Show the receptacle outlets with 4 foot spacing.

The bathroom requires a dedicated 20 AMP circuit.

Living and Bedrooms require all wall locations within 6 feet from a receptacle outlet.

All 15 and 20 AMP circuits without GFCI propection require Arc Fault breakers.