Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM02868
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2022 | PAUL CAMARENA | ZONING | REVIEW | Passed | |
| 04/20/2022 | PCAMARE1 | ENGINEERING | REVIEW | Passed | |
| 04/20/2022 | PCAMARE1 | NPPO | REVIEW | Passed | |
| 04/20/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Provide a panel schedule with circuit sizes. Show kitchen countertops with two 20 AMP circuits. Show the receptacle outlets with 4 foot spacing. The bathroom requires a dedicated 20 AMP circuit. Living and Bedrooms require all wall locations within 6 feet from a receptacle outlet. All 15 and 20 AMP circuits without GFCI propection require Arc Fault breakers. |