Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2022 PCAMARE1 OIP REVIEW Approved
06/23/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02861

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Denied
Main breaker replacement may not negatively affect the equipment integrity or listing, NEC 110.3. Provide an electrical load calculation if reducing the main breaker rating.


PLUMBING REVIEW COMMENTS:
N/A