Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM02856
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/14/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | 1. Show the door from a garage to dwelling with a 20-minute fire rating (or 1-3/8” solid core) with self-closing and self-latching provision, R302.5.1. 2. Ducts serving a dwelling may not have openings into the garage, R302.5.2. Remove the extended duct (Toxic gas passage). A garage may have a separate HVAC unit such as a mini split. 3. Show a ½" gypsum board (garage side) on all walls common to the garage and house or other fire rated product in compliance with R302.6. The dwelling side also requires ½" gypsum board for controlling fire spread. |
| 07/15/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved |