Permit Number: T22CM02840
Parcel: 101211390

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM02840
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM02840
Detached garage
5160 N GRACIOUS CT Zoning RX-1

TRANSMITTAL DATE:? April ?19, 2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Clarify if any grading is to be proposed.
2.COMMENT:. Per Unified Development Code (UDC) TABLE 6.3-1.A: DIMENSIONAL STANDARDS FOR THE RH, SR, SH, RX-1, & RX-2 ZONES, RX-1 Zone the required perimeter yard setback from the proposed storage Garge to the south property line is 20’-0”, proposed perimeter yard setback is 15’-0”. At a minimum a neighbor’s setback waiver is required to reduce the perimeter yard setback. To secure this waiver the following text shall be provided on the plot plan and be signed and dated by the only of the property to the south:
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________

If you are unable to secure the neighbor’s setback waiver a Design Development Option (DDO) will need to be processed and approved to reduce the setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.



3.COMMENT: Per UDC section 6.6.3.D. Accessory structures, except for accessory dwelling units , shall not exceed 12 feet in height unless attached to a principal structure . If attached to the principal structure , maximum height permitted shall be the same as for the principal structure. Demonstraight how the standard above is satisfied.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
04/19/2022 IMONSHI1 ENGINEERING REVIEW Passed
04/19/2022 IMONSHI1 NPPO REVIEW Passed
05/04/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02840
GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
No mechanical work has been included as part of this submittal


ELECTRICAL REVIEW COMMENTS
Denied
1. Provide a gfci outlet within 3’ for the new powder room sink. 2017 NEC 210.52 (D). A 20-amp branch circuit is required for the powder room to supply the outlet and shall have no other outlets on the circuit. 2017 NEC 210.11(C) (3).
2. Indicate a light and switch for the new powder room. 2017 NEC 210.70(A)(1).
3. Indicate the location of the switch for the exterior lighting at the garage door.
4. Note that all 15- and 20-amp outlets shall be tamper proof type. 2017 NEC 210.52.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No plumbing work has been included as part of this submittal