Permit Number: T22CM02822
Parcel: 121093720

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02822
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM02822

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Return air shall be approximately the same as supply air. Provide more return air grills sheet M1 (IMC 2018 403.1 & 601.5 item 4) Response: Additional return air grilles are not required. Return air grilles and ductwork are designed by a registered design professional and meet code requirements. you have no return air grilles in the waiting room and phot rooms Complied
2. Provide cfm ratings for all return air grills sheet M1 (IMC 2018, 206.3.1) Response: CFM ratings are provided for return air grilles in the ambulatory occupancy side of the building. CFM ratings are not required to balance the return grilles for the medical office occupancy side of the building. 1. the air balance report is required for both sides and 2 sufficient return air is addressed in the code, and that is why, this information is required in the review process. Complied
3. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov