Permit Number: T22CM02820
Parcel: 13320097A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM02820
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM02820
Carport Extension
6426 E PRINTER UDELL Zoning R-1

TRANSMITTAL DATE:April 19, 2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Provide a Residential Plot Plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. This shall in include:
a. Lot coverage calculation that meets the requirements of UDC Article 6.4.3 & the example shown on the residential plot requirements.
b. Zoning of adjacent parcels
c. All Utility lines
d. Property line distances

2.COMMENT: Draw dimension and label the height of the new structure measured from design grade to top of wall.




If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
04/19/2022 WBERGER1 ENGINEERING REVIEW Passed
04/19/2022 PCAMARE1 NPPO REVIEW Passed
05/04/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02820

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide the structural design information on the plans including the proposed live and dead loads and any required wall bracing.
2. Provide a foundation plan of the new extension including dimensions. Indicate the locations of the new concrete piers as well as information on the existing foundation that will be used for support.
3. Provide a roof framing plan including dimensions for the new extension. Indicate the on center spacing for the new 2x6 rafters and the grade of lumber to be used on the project (for example Douglas fir or Southern Pine, grade #2 or better).
4. Clarify if the existing ridge is the same size (triple 2x12) or if it different. It appears to be larger in the drawings.
5. Provide a detail on how the new 2x6 rafters will be tied to the new triple 2x12 beams. Note any hangers or collar ties to be installed.


BUILDING REVIEW COMMENTS:
Denied
1. Note on the drawings that all work will be done in accordance with the adopted codes for the City of Tucson.
2. Clarify if this is an extension of an existing open carport or an extension of an enclosed shop area. The notes reference both.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
No mechanical work was included in this submittal.


ELECTRICAL REVIEW COMMENTS
Denied
1. Clarify if there will be any electrical installed as part of this permit, none is indicated on the plans. If electrical is desired, provide an electrical plan.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No plumbing work was included as part of this submittal.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov