Permit Number: T22CM02811
Parcel: 131010400

Address:
4984 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM02811
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2022 JPEELDA1 FIRE REVIEW Reqs Change Plans shall have a cover sheet that includes but not limited to:
The scope of work
Code references
Occupancy type
Occupant load
Type of construction
If the building has a fire sprinkler and or fire alarm system

Plans shall show an egress plan for the new spaces that also indicates the travel distances

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
04/27/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM02811
4984 E 22nd St – C-2
Building Addition (1st Review)

TRANSMITTAL: April 27, 2022

Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Animal Services is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standards 4.9.4.D.1, .2, .3, & .4 and 4.9.13.P or 4.9.4.D.7 & 4.9.4.D.10-.15.

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. As Development Package DP17-0218 is still open a revision to this DP is required showing the proposed addition. This revision must be approved prior to approval the building permit.

If you have any questions about this transmittal, please contact Nicholas Ross at Nocholas.Ross@tucsonaz.gov.
04/27/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that the proposed condensate drains terminate at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.
04/27/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/27/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
04/27/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A3.0: Please provide structural calculations for the addition. In addition, provide general structural notes indicating material strengths, design loadings, and required special inspections.
2. Sheet A6.2; Fencing: Please provide fencing details as required (post spacing and foundation, rail connections, etc.).
3. Sheet A7.10; Section 3: Please provide details as required (bulkhead framing connections, connection to existing wall, etc.).
4. General: Please provide a site plan per Section 107.2.6 of the IBC.
5. General: Please provide with the site plan a project narrative per Section 107.2.1 of the IBC.
6. General: Please provide with the site plan a code analysis indicating the size of the project (SF), Construction Type, Occupancy Classification, Occupant Load, and sprinkler system (if required).
7. General: Please provide with the site plan the current code references for this project.
8. General: Please provide with the site plan special inspections required.
9. General: Please provide written responses to all review comments.
04/27/2022 ROBERT SHERRY WATER REVIEW Completed
04/27/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/12/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a detail narrative as to the scope of electrical work proposed this submittal and correlate electrical with Mechanical/Plumbing plans where applicable.
Ref; 2018 IBC 107.2.1, 2017 NEC