Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM02811
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Plans shall have a cover sheet that includes but not limited to: The scope of work Code references Occupancy type Occupant load Type of construction If the building has a fire sprinkler and or fire alarm system Plans shall show an egress plan for the new spaces that also indicates the travel distances Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |
| 04/27/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM02811 4984 E 22nd St – C-2 Building Addition (1st Review) TRANSMITTAL: April 27, 2022 Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-2 zone (UDC 4.7.21). Animal Services is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standards 4.9.4.D.1, .2, .3, & .4 and 4.9.13.P or 4.9.4.D.7 & 4.9.4.D.10-.15. 1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. As Development Package DP17-0218 is still open a revision to this DP is required showing the proposed addition. This revision must be approved prior to approval the building permit. If you have any questions about this transmittal, please contact Nicholas Ross at Nocholas.Ross@tucsonaz.gov. |
| 04/27/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Verify that the proposed condensate drains terminate at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. |
| 04/27/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/27/2022 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | See Zoning comments |
| 04/27/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A3.0: Please provide structural calculations for the addition. In addition, provide general structural notes indicating material strengths, design loadings, and required special inspections. 2. Sheet A6.2; Fencing: Please provide fencing details as required (post spacing and foundation, rail connections, etc.). 3. Sheet A7.10; Section 3: Please provide details as required (bulkhead framing connections, connection to existing wall, etc.). 4. General: Please provide a site plan per Section 107.2.6 of the IBC. 5. General: Please provide with the site plan a project narrative per Section 107.2.1 of the IBC. 6. General: Please provide with the site plan a code analysis indicating the size of the project (SF), Construction Type, Occupancy Classification, Occupant Load, and sprinkler system (if required). 7. General: Please provide with the site plan the current code references for this project. 8. General: Please provide with the site plan special inspections required. 9. General: Please provide written responses to all review comments. |
| 04/27/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/27/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 05/12/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide a detail narrative as to the scope of electrical work proposed this submittal and correlate electrical with Mechanical/Plumbing plans where applicable. Ref; 2018 IBC 107.2.1, 2017 NEC |