Permit Number: T22CM02773
Parcel: 13727989A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02773
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Completed
07/18/2022 ROBERT SHERRY WATER REVIEW Reqs Change Water Comments:

Unless the backflow preventer shown at the water service entrance to the building on sheet P-3 and in detail 12 on sheet P-5 is in addition to the existing backflow preventer located after the water meter, revise the drawings to reflect the actual work to be done. If the additional backflow preventer is to be installed, revise the water pressure calculations as needed. [Initial comment: Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities and are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf.]
08/03/2022 JVINCEN1 FIRE REVIEW Approved