Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM02773
Parcel: 13727989A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM02773
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02773

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Sheet CS: It appears that the IEBC is being used lieu of the IBC. One is free to use either code but not both, unless specifically referenced by the IEBC. If the IEBC is the desired approach, one must choose 1 of 4 compliance paths. These compliance paths cannot be used in combination with each other in accordance Section 301.3 of the IEBC. It is important to note that the Chapter 3 requirements apply to all compliance methods.
1. Prescriptive compliance method: Chapter 5: The prescriptive approach is the simplest method to follow in terms of code requirements, but is also the most conservative approach.
2. Work area compliance method: Chapters 6-12:The work area compliance method provides the greatest amount of benefits to the building owner and design professional. This is the easiest route to take. It is much more conservative.
3. Performance compliance method: Chapter 13: This method focuses on what the building is required to do, rather than prescribing how it is to be constructed. This method requires the design profession to work more closely with the owner of the building, as well as the code official, to ensure that design meets specific requirements for the occupants and not simply the prescriptive requirements.
4. Previously adopted code: Section 301.3 Exception 1. This method utilizes a previously adopted code under which the area in question was most recently built or modified; this requires the code official’s approval.
Please clearly indicate which compliance method has been chosen and provide a narrative outlining the applicable code requirements.
1. Provide a thorough egress plan that includes the furniture plan and show all exiting paths and travel distance measurements.
2. Indicate the location of egress illumination on the RCP in accordance with Section 1008.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/26/2022 SSHIELD1 ENGINEERING REVIEW Passed
04/26/2022 STEVE SHIELDS ZONING REVIEW Approved
04/26/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/29/2022 JVINCEN1 FIRE REVIEW Reqs Change See building comments.

john.vincent@tucsonaz.gov
5203495581
05/09/2022 ROBERT SHERRY WATER REVIEW Reqs Change Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities and are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/10/2022 VVERA1 OUT TO CUSTOMER Completed