Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM02770
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/27/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/02/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide ventilation (i.e. outdoor air) for the dwelling unit per Section 403.3.2.1, IMC 2018. |
| 05/02/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/10/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Provide for replaced receptacles to be tamper resistant type per NEC 210 and 406.12. 2. All replaced luminaires to comply with 2018 IECC section R404.1. 3. This is a commercial project. Please remove references to the IRC. 3. Any modified branch circuits shall comply with NEC 210.12D. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/10/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |