Permit Number: T22CM02764
Parcel: 13345222A

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM02764
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Provide a complete panel schedule including load calculations.

2. Indicate wiring methods for the branch circuits.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/10/2022 NGARCIA3 OUT TO CUSTOMER Completed