Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM02750
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2022 | PCAMARE1 | OIP | REVIEW | Approved | |
| 06/22/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM02750 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Plans do not include deadload calculations. 2018 IRC - 301.1. Provide structural calculations showing the existing roof system is capable of supporting the additional dead loads of the PV system. BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Conditionally Approved 1. Clarification of line side tap. 2017 NEC - 705.31. The maximum length of the tap conductors is 10'. The note on pg. PV-6 indicates max. 10' from the PV disconnect to the tap connection where this should reference the total unprotected conductor (tap) length. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/23/2022 | VVERA1 | OUT TO CUSTOMER | Completed |