Permit Number - T22CM02642
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Completed | |
| 10/05/2022 | PAUL CAMARENA | ZONING | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: T22CM02642 Sleeping quarters 1467 W DELAWARE ST Zoning R-2 TRANSMITTAL DATE:?October 5, 2022 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: Draw and dimension the height of the accessory structure Per UDC section 6.4.4.A. “Building height is the vertical distance measured from the design grade elevation to the highest point of a flat roof; to the deck line of a mansard roof; or to the middle (between the eave and ridge ) of the highest gable of a pitched or hipped roof, except as follows: (See Figure 6.4.4-A, Measurement of Building Height .)” 2.COMMENT: Per UDC section 6.6.3.D “Accessory structures , except for accessory dwelling units , shall not exceed 12 feet in height, unless attached to a principal structure . If attached to the principal structure , maximum height permitted shall be the same as for the principal structure” If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |