Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM02531
Parcel: 127022790

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM02531
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0.0; Exiting Plan: Per the IBC Section 1017.3, the measurement of the exit access travel distance shall be along the natural and unobtrusive path of horizontal and vertical egress travel. Please revise the exit paths to meet that requirement.
2. Sheet A1.0; New Work Keynotes: Please provide the new wall stud gauge and spacing in the New Work Keynote 1.
3. General: Please provide written responses to all review comments.
04/20/2022 SSHIELD1 ENGINEERING REVIEW Passed
04/20/2022 STEVE SHIELDS ZONING REVIEW Approved
04/20/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/21/2022 JVINCEN1 FIRE REVIEW Approved
04/26/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/26/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that the mechanical design provides return ducts as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018.
04/26/2022 ROBERT SHERRY WATER REVIEW Completed
05/02/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 . Designing the site Electrical constitutes the practice of engineering. Provide complete electrical plans including a luminaire schedule that correlates with the lighting and power floor plans, panel schedules, 2018 IECC compliance, tamper resistant receptacles where applicable per NEC 406.12, compliance with NEC art 517.13, plans sealed by an EE. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC. 2012 Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.