Permit Number: T22CM02512
Parcel: 133086320

Address:
8240 E KEUKA CT

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02512
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Due to the new interior work for the accessible restroom, this will add new comments and requirements.
1. Sheet A3; Detail 2: Please provide bracing at the top of the new interior partition. Indicate bracing size, spacing, and connection to the top of the partition and to the structure above.
2. General: Please provide a valuation (labor + materials) for the revision to the new accessible restroom.
3. General: Reviews must now be completed for the plumbing and electrical work in the new accessible restroom.
4. General: Please provide written responses to all review comments.
04/20/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Reduced pressure backflow prevention assemblies are required at the water meter for licensed, personal care facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
2. Provide the size of the water meter serving this building and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
3. Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Reference: Section 419.6, IPC 2018 as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
4. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
5. If the new shower does not have a prefabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 421.5, IPC 2018.
6. Provide shower valves that comply with the requirements of Section 412.3, IPC 2018.
7. Verify that the distance from the hot water source to the hot water termination for the new lavatory complies with the requirements of Section C404.5, IECC 2018.
04/20/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide calculations to show that adequate ventilation is being provided for the building. Reference: Section 403.3.1, IMC 2018.
05/02/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/10/2022 JPEELDA1 FIRE REVIEW Approved