| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/05/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G1 (Code Check); Sheet A1 (Floor Plan): The Code Check indicates this is an R-1 with 20 occupants. The Floor Plan indicates 5 bedrooms with 8 beds. The occupant load should be based on the bedroom sizes and capacities. Use 80 SF for one occupant in a bedroom, and 120 SF for two occupants in a bedroom to determine the total occupant load. As indicated on the Floor Plan, it would be 8 occupants. This would change the Occupancy Classification to an R-4. Please verify. 2. Sheet A1; Floor Plan: Please verify and indicate on the drawings the requirements of Section 305.8.10 of the 2018 IEBC are met for accessible restrooms provided. 3. General: Please provide written responses to all review comments. |
| 04/05/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/06/2022 | ENEWCOM1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/06/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |