Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2022 IMONSHI1 OIP REVIEW Reqs Change FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T22CM02508 / Solar

Plot Plan Review (1st Review)

2421 E 8TH ST/ R-1 Zone

TRANSMITTAL DATE: 05/19/2022



Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



1.COMMENT: Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). Show the backfeed breaker incompliance with the bus limitation or increase the service panel rating.