Review Details: CELL TOWER/ANTENNAS
Permit Number - T22CM02505
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/06/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-3; New Southwest Elevation: A boxed note indicates a structural analysis is being performed for all upgrades to existing construction shown. No analysis was located in this submittal for the structural adequacy of the existing 21'-0" tall light pole for the additional antennas indicated. Please provide. 2. General: Please provide a Special Inspections Certificate with Parts A and B completed for the epoxy anchors (at new antenna mounts). |
04/06/2022 | VFLORES1 | COMMUNICATIONS | REVIEW | Approved | |
04/08/2022 | IMONSHI1 | PLANNING-CITY HALL | REVIEW | Completed | |
04/08/2022 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
04/08/2022 | IMONSHI1 | ZONING | REVIEW | Approved | |
04/11/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
05/02/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/02/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |