| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/05/2022 | GSLEIGH1 | OIP | REVIEW | Reqs Change | COMMENT: Please see attached templates and resubmit. The pipe is undersized based on a developed length of 130' the demand supplied is 82k BTU. Pipe must be same size to first appliance T-Connection (Water Heater). Please provide specific lengths between appliances. Capped future use stub requires estimated BTU and length for use. https://www.tucsonaz.gov/files/pdsd/permits/Gas%20Piping%20Template.pdf https://www.tucsonaz.gov/files/pdsd/permits/Sample%20Gas%20Template.pdf |