Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T22CM02458
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/05/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/06/2022 | VFLORES1 | COMMUNICATIONS | REVIEW | Approved | |
04/08/2022 | IMONSHI1 | PLANNING-CITY HALL | REVIEW | Completed | |
04/08/2022 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
04/08/2022 | IMONSHI1 | ZONING | REVIEW | Approved | |
04/11/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
04/28/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/28/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |