Permit Number: T22CM02457
Parcel: 13323194A

Address:
770 N KOLB RD

Review Status: Active

Review Details: RESUBMITTAL

Permit Number - T22CM02457
Review Name: RESUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/31/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Completed Activity Number: T22CM02457

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Denied
E5.1 Electrical Schedules and Diagrams: Need to obtain or callculate short circuit value for utility transformer. Also need to show length of conductors in Feeders schedule. Provide a sample calculation for short circuit value for Panel A. Then determine if any panels have insufficient KAIC rating for new design.


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/31/2022 WBERGER1 ZONING REVIEW Completed ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM02457
770 N Kolb Rd - PAD-3
Remodel existing structure to be self-storage (2nd review)

TRANSMITTAL: June 22, 2022
This site is in PAD-3 (UDC 4.7.24 and 3.5.5).

1. This comment was not addressed. Per UDC 3.3.3.G.2.c, as the existing development is proposed to undergo a change of use, a Development Package that meets the requirement of Administrative Manual 2-06 is required. DP22-0060 must be approved prior to the approval of this permit.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov.
08/31/2022 WBERGER1 ENGINEERING REVIEW Completed See Zoning comments.
12/30/1899 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active