Permit Review Detail
Review Status: Active
Review Details: RESUBMITTAL
Permit Number - T22CM02457
Review Name: RESUBMITTAL
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/31/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 08/31/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Completed | Activity Number: T22CM02457 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Conditionally Approved Approved/Subject to field approval ELECTRICAL REVIEW COMMENTS Denied E5.1 Electrical Schedules and Diagrams: Need to obtain or callculate short circuit value for utility transformer. Also need to show length of conductors in Feeders schedule. Provide a sample calculation for short circuit value for Panel A. Then determine if any panels have insufficient KAIC rating for new design. PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 08/31/2022 | WBERGER1 | ZONING | REVIEW | Completed | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM02457 770 N Kolb Rd - PAD-3 Remodel existing structure to be self-storage (2nd review) TRANSMITTAL: June 22, 2022 This site is in PAD-3 (UDC 4.7.24 and 3.5.5). 1. This comment was not addressed. Per UDC 3.3.3.G.2.c, as the existing development is proposed to undergo a change of use, a Development Package that meets the requirement of Administrative Manual 2-06 is required. DP22-0060 must be approved prior to the approval of this permit. If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov. |
| 08/31/2022 | WBERGER1 | ENGINEERING | REVIEW | Completed | See Zoning comments. |
| 12/30/1899 | ANY | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Active |