Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM02456
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/06/2022 | PAUL CAMARENA | ZONING | REVIEW | Approved | |
| 04/06/2022 | PCAMARE1 | NPPO | REVIEW | Passed | |
| 04/20/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | An unprotected roof overhang may not extend closer than 24 inches to the neighboring property line. Any part of a roof projection extending into the 3-foot fire separation distance from the property line requires not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). Compliance with R302.1 (City of Tucson Amended) can be achieved by removing the porch roof within 3 feet to the property lines or provide a complete wall barrier (ground to roof and end to end) with not less than one-hour fire-resistive construction in compliance with IBC Table 721.1(2). Any part of a roof projection extending into the 3-foot fire separation distance from the property line requires not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). Provide updated plans showing fire spread compliance. |
| 05/19/2022 | PCAMARE1 | ENGINEERING | REVIEW | Passed |