Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM02420
Parcel: 115043680

Address:
522 E HELEN ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM02420
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM02387
1001 S Van Buren Ave - R-1
ADU (1st Review)

TRANSMITTAL: April 5, 2022

This site is located in the NR-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.

1. Provide a floor plan for the existing residence so that it can be determined if the requirements of UDC Article 4.9.7.B.7 are applicable. For your information all four (4) of the rooms shown on the plan are considered a bedroom, see UDC Article 11.4.3 Definition of a Bedroom.

2. Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. As no dimension from design grade to the highest point of the wall, where wall meets the eave were provided Zoning cannot verify perimeter yard setback requirements.

3. As primary access to the vehicle parking area, carport, is proposed demonstrate on the plan that the requirements of UDC Article 7.4.6.K.2 are met.

COMMENTS: the following comments are relative to an application for NPZ Review (UDC 5.10.3).

This site is located in the NR-1 zone (UDC 5.10.3). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 – 9.

4. Prior to zoning approval an NPZ review and approval is required. Owner is proposing to construct an attached four (4) bedroom addition. The property fronts on one local street Helen Street. Structure appears to meet setbacks and is located in the rear yard.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov
04/05/2022 SSHIELD1 ENGINEERING REVIEW Passed
04/05/2022 SSHIELD1 NPPO REVIEW Passed
04/29/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02420


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. 2018 IRC Section E3901.3.1, E3901.4.1. Clarification needed. Revise plans to clarify the location of the dishwasher and under-counter refrigerator electrical connections. The dishwasher is not permitted to be on the same circuit as the (2) required small appliance branch circuits. If the receptacle outlets shown (to the left of the sink) are installed below the counter for the connection of the appliances, show that correct receptacle outlet spacing has been provided for above the countertop.
2. 2018 IRC Section E3902.9. Revise the plans to show that GFCI protection has been provided in the laundry area (ckt 13) and for the dishwasher. Electrical note #38 indicates GFCI protection is required, but the plans do not indicate how this has been provided for.


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
04/30/2022 DBENOIT1 APPROVAL SHELF Completed
04/30/2022 DBENOIT1 OUT TO CUSTOMER Completed
04/30/2022 DBENOIT1 REJECT SHELF Completed