Permit Number: T22CM02408
Parcel: 11517204C

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM02408
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2022 PCAMARE1 OIP REVIEW Reqs Change Transmittal Template


FROM: Paul Camarena
PDSD Residential Review Section

PROJECT:T22CM02408
Roof top Solar Panels (1st Review)
(1379 W YAVAPAI ST

TRANSMITTAL DATE: May 19, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


? COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments.

COMMENT: The Plan Set shows a line-side tap, Line taps require compliance with NEC 230.46. Update the plans showing a tap enclosure with sufficient space for the tap device, or show a meter socket extension with tap terminals (approved Milbank tapping device)


COMMENT: Since the modules are installed on a manufactured home an engineered sealed plan is required. Please include structural calculations.

? COMMENT: Residential will review the application on the next submittal




If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.Camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans