Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM02394
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The maximum distance between a public lavatory faucet and its hot water source is 2-feet per Section C404.5.1, IECC 2018. Revise the design as appropriate. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] 2. Correct the total gas load (7 x 128 = 896, not 1280). [Initial comment: Coordinate the number and type of dryers with the architect. The architect shows only 14 dryers, and each dryer has only one dryer pocket and one exhaust. Verify the gas input requirements for each type of dryer from the manufacturer. Reference: Section 303.1, IFGC 2018.] |
| 09/12/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 09/12/2022 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Comment not resolved. Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded [Initial comment: Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.] |
| 09/20/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. The building shall have only one electrical service per NEC 230.1, 230.40. Verify that the emergency battery back-up lighting complies with NEC art 700.12F(2)(3). (Unswitched branch circuit from area lighting). Revise the 2012 IECC calculations to the current 2018. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |