Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM02394
Parcel: Unknown

Address:
3024 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM02394
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2022 WBERGER1 ZONING REVIEW Approved
04/05/2022 WBERGER1 ENGINEERING REVIEW Passed
04/05/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/05/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/06/2022 JPEELDA1 FIRE REVIEW Approved
04/19/2022 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
04/20/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Information regarding the municipal water supply should be obtained from Tucson Water, not the Gilbert Water Department.
2. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
3. Coordinate the number and type of dryers with the architect. The architect shows only 14 dryers, and each dryer has only one dryer pocket and one exhaust. Verify the gas input requirements for each type of dryer from the manufacturer. Reference: Section 303.1, IFGC 2018.
04/20/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the number and type of dryers with the architect. The architect shows only 14 dryers, and each dryer has only one dryer pocket and one exhaust. Verify the exhaust requirements for each type of dryer from the manufacturer. Reference: Section 303.1, IFGC 2018
04/28/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Provide complete load calculations for the electrical service. Verify that the existing electrical service equipment utilized and riser conductors are adequate for any increased load for the new 400 amp disconnect and downstream equipment.

2. Verify that the emergency battery back-up lighting complies with NEC art 700.12F(2)(2).

Ref; 2018 IBC section 107.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements