Permit Number: T22CM02376
Parcel: 133323280

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02376
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM02376


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
Truss drawings to be provided as a differed submittal.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
All gas lines will be pressure tested in accordance with 2018 IRC G2417.1 prior to concealing.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Conditionally Approved
All plumbing drain, waste and vent systems shall be tested for leaks in accordance with the 2018 IRC P2503.5 prior to concealing


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov