Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM02363
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. The new panel āCā panel schedule show numerous electrical equipment connected to it. Please provide a complete electrical power and lighting floor plan showing all the devices and equipment, branch circuit/panel designations. 2. Label the load summary table as to the origin of the loads. Ref; 2018 IBC section 107.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/26/2022 | VVERA1 | OUT TO CUSTOMER | Completed |