Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM02346
Parcel: 136230440

Address:
3441 S BIRCH AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM02346
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2022 IMONSHI1 NPPO REVIEW Passed
03/31/2022 IMONSHI1 ENGINEERING REVIEW Passed
04/12/2022 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T22CM02346 / Carport Enclosure

Plot Plan Review (1st Review)

3441 S Birch Av/ R-2 Zone

TRANSMITTAL DATE: 04/12/2022



Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



1.COMMENT: Provide setback dimensions for the north and west property line on the site plan on the next submittal. Setback is measured from structure to the property line

2.COMMENT: Remove aerial image from site plan.



For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
04/25/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02346

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide the structural design information on the plans that is in compliance with 2018 IRC R301.2(1). Include the proposed live and dead loads for the structure and any required wall bracing.
2. Note on the drawings that fire blocking will be installed in all walls and concealed spaces where newly built or existing areas in which the framing is exposed during construction. 2018 IRC R302.11.


BUILDING REVIEW COMMENTS:
Denied
1. Indicate the location of a second egress door from the house that is a minimum of 36” wide OR modify the design to accommodate a 36” new front door. Door Number 1 is indicated as being 30” wide on the door schedule. 2018 IRC R311.2.
2. Provide natural light and venting information for the new bedroom. 2018 IRC R303.1.
3. Provide the U value and SHGC for the new windows on the drawings per the 2018 IECC Table R402.1.2 for climate zone 2.
4. Indicate the location of the egress window and its operational type on the drawing. Every room used for sleeping purposes shall contain an egress window per 2018 IRC R310.2. Since this is a grade floor opening, only 5 sf of net clear opening is required.
5. Clarify the insulation type top be used for the ceiling, a standard batt insulation will not fit in a 2x6 rafter. 2018 IECC R402.2.2.


MECHANICAL REVIEW COMMENTS:
Denied
1. Note on the drawings that the new mini-split mechanical system will be installed in accordance with manufactures specifications


ELECTRICAL REVIEW COMMENTS
Denied
1. Provide a line diagram for the new load center upgrade including is grounding and bonding information.
2. Note on the drawing that a minimum of 90% of all new lighting fixtures in the dwelling will contain high-efficacy lamps. 2018 IECC R404.1.
3. Note on the drawing that all new or replaced 15- and 20-amp outlets shall be tamper proof type. 2017 NEC 210.52.
4. Note on the drawing that all exterior outlets shall be GFCI protected and be provided with a weatherproof enclosure with “in-use” covers. 2017 NEC 406.8.
5. Indicate the location of the smoke detectors in the existing house. Smoke detectors shall be installed in each sleeping room, outside of each sleeping room in the immediate vicinity of the bedroom. 2018 IRC R314.2.
6. Note on the drawings that all smoke detectors shall receive their primary power from the building wiring with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4.
7. Indicate the location of carbon monoxide detectors in the existing house. Carbon monoxide detectors shall be installed outside of each sleeping area in the immediate vicinity of the bedrooms. 2018 IRC R315.3.
8. Note on the drawings that carbon monoxide devices shall receive their primary power from the building wiring with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4. Smoke detectors and carbon monoxide alarms may be combined.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No plumbing work was included as part of this submittal.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov