Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T22CM02338
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2022 | ARUIZ1 | OIP | REVIEW | Reqs Change | COMMENT: Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). Show the backfeed breaker incompliance with the bus limitation or increase the service panel rating. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/19/2022 | VVERA1 | OUT TO CUSTOMER | Completed |