Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2022 ARUIZ1 OIP REVIEW Reqs Change TRANSMITTAL DATE: July 13 , 2022
Revision 2

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.

COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: Identify Buss connector for maintaining panel UL listing. Verify from Manufacturer of panel that performing this type of tap will not void the listing. Or have a NRTL listing agency perform a field evaluation of the equipment after tap is performed to recertify the listing of equipment.

COMMENT: Residential will review the application on the next submittal

If you have any questions about this transmittal, Contact Angie.Ruiz@Tucsonaz.gov any time during the week by email

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2022 VVERA1 OUT TO CUSTOMER Completed