Permit Number: T22CM02296
Parcel: 131112160

Address:
5710 E 32ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02296
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Items built without permit may require alteration or improvement for code compliance with the 2018 IRC, R105. Show the as-built ramada construction plans with necessary alterations for achieving 20128 IRC code compliance.

The ramada roof may not extend to a point closer than 3 feet from the neighboring property line without fire rated protection. Provide compliance with R302.1 (City of Tucson Amended) by removing the porch roof within 3 feet to the property line or provide a complete wall barrier with not less than one-hour fire-resistive construction in compliance with IBC Table 721.1(2).
07/06/2022 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T22CM02296
5710 E 32nd St
Enclose carport to den (2nd Review)

TRANSMITTAL DATE: July 6, 2022

COMMENTS: This site is in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-4), subject to use-specific standard 4.9.7.B.5-9.

1. This comment was not addressed. For any single-family residence with five bedrooms, three parking spaces are required (4.9.7.B.7). Provide a floor plan of the entire residence. For clarification, the den counts as a bedroom per UDC 11.4.3.

2. This comment was not addressed. The attached back porch of the residence appears on aerial photography beginning in 2016. Either provide permit documentation of this porch or include it within this permit's scope of work.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.