Permit Number: T22CM02288
Parcel: 107050590

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM02288
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2022 ARUIZ1 OIP REVIEW Reqs Change PROJECT: T22CM02288
Roof top Solar Panels (1st Review)

TRANSMITTAL DATE: May 16, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.

COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: The Plan Set shows a tap, Identify type of connector for maintaining UL listing, require compliance with NEC 230.46.

COMMENT: Verify the truss load carrying capacity. M1401.

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Angie.Ruiz@Tucsonaz.gov any time during the week by email

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
05/16/2022 NGARCIA3 OUT TO CUSTOMER Completed