Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM02265
Parcel: 11615085A

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM02265
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Assign branch circuits and panels for the devices and equipment that correlate with the panel schedules. Include load calculations associated with the scope of work. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2022 VVERA1 OUT TO CUSTOMER Completed