Permit Number: T22CM02262
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02262
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02262

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. The Truss calculations show end reactions of trusses exceeding the capacity of the hangers used. Verify if hangers have been revised with appropriate capacity.

BUILDING REVIEW COMMENTS:
Conditionally Approved
1. Additional exit lighting may be required upon inspection.

MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Correction Complied
2. Approved/Subject to field approval

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E5.1 PANEL SCHEDULES and CALCULATIONS: Confirm that DP1 panel is large enough to handle the additional loads of panels LA and LB. May need to upsize DP1 to a 350-400 amp MCB and feeders to match MCB.

PLUMBING REVIEW COMMENTS:
Approved