Permit Number: T22CM02259
Parcel: 113103980

Address:
1628 E SPRING ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM02259
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM02259
Addtion
1628 E SPRING ST Zoning R-1

TRANSMITTAL DATE:?March ?29,2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Draw label and dimension the height of the building on the elevation sheets in order to verify the setbacks . Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A.

2.COMMENT: In the R-1 ZONE, a single family residence is subject to UseSpecific Standards 4.9.7.B.7 “ For any new single-family dwelling in the R-1 zone with five bedrooms , three parking spaces are required.For every bedroom over five, one additional space is required for each bedroom . For all single-family dwellings in the R-1 zone with five or more bedrooms , and for all lots containing two or more single-family dwellings, with the second dwelling having more than one bedroom , all parking spaces must be located on-site , either in a side or rear perimeter yard . Parking spaces may not be located in a vehicular use area in any front street perimeter yard . A parking area is not required to be developed to a commercial standard. A dustproof parking surface is required to at least a minimum of two inches of compacted pea gravel. An existing covered residential parking area may be used." With that being said parking will be required.




If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
04/08/2022 PCAMARE1 NPPO REVIEW Passed
04/21/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02259

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Update the roof framing notes on sheet A2 for the attic access to indicate the 2018 IRC, not the 2012 IRC.
2. Update the design criteria general note 14 on sheet SP-1 in the specifications that indicates Oro Valley and show the requirements for Tucson per the 2018 IRC table R301.2(1) amendment.
3. Update the wood truss note A and B to indicate the 2018 IRC and remove the reference to Oro Valley.


BUILDING REVIEW COMMENTS:
Denied
1. Provide drawings that contain a stamp and seal from a state licensed architect or structural engineer.
2. Correct the energy compliance note on sheet A1 that is partially obscured by the other notes. Clarify if the certificate is to be installed in the garage near the water heater, the water heater does not appear to be in this location.
3. Provide natural light and venting information for all proposed rooms and existing rooms that are to be modified. 2018 IRC R303.1.
4. Note that fire blocking will be installed in all walls and concealed spaces (including the existing truss roof) where newly built or existing areas in which the framing is exposed during construction. 2018 IRC R302.11.


MECHANICAL REVIEW COMMENTS:
Denied
1. Note that ducts, air handlers and filter boxes shall be sealed. 2018 IRC M1601.4.1.
2. Note on the drawings that the new ducts will be tested for air leakage in accordance with 2018 IECC R4503.
3. Note on the drawings that the gas lines will be pressure tested in accordance with 2018 IRC G2417.1.
4. Note on the drawings that all bath fans will be exhausted directly to the exterior. 2018 IRC M1505.2.


ELECTRICAL REVIEW COMMENTS
Denied
1. Note on the drawing that the outlet box for the new ceiling fan will be listed and labeled as being a fan rated box capable of supporting 70lbs. 20107 NEC 314.27(C)


PLUMBING REVIEW COMMENTS:
Denied
1. Update the plumbing notes on sheet P1 that references plumbing fixtures will have water saving devices in accordance with Oro Valley.
2. Note on the drawings that toilets are required to be low flush using 1.6 gallons per flush or less, while showerheads and faucets must not exceed 2.5 gallons a minute. Ordinance 7178.
3. Note on the drawings that all plumbing drain, waste and vent systems shall be tested for leaks in accordance with the 2018 IRC P2503.5 prior to concealing.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/21/2022 PCAMARE1 ENGINEERING REVIEW Passed
04/21/2022 JPEELDA1 FIRE REVIEW Approved