Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM02239
Parcel: 140221130

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02239
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2022 CVASQUE2 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change PLEASE CONTACT PC ADDRESSING BUILDING NUMBER NEEDS TO BE ASSIGNED PRIOR TO ISSUANCE Ph# 520-724-9512, EMAIL:ADDRESSING@PIMA.GOV
09/08/2022 PCAMARE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
09/08/2022 PAUL CAMARENA ZONING REVIEW Reqs Change REVIEW TRANSMITTAL

FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM02227, T22CM02228, T22CM02229, T22CM02230, T22CM02231, T22CM02232, T22CM02233, T22CM02234, T22CM02235, T22CM02236 T22CM02237,T22CM02238, T22CM02239
Multi-Family0020
1701 E VALENCIA RD Zoning C-2

TRANSMITTAL: September 8, 2022.

1. Zoning has reviewed the building plans for compliance with the associated unapproved Development Package DP22-0029. Zoning cannot approve the building plans until the DP is approved.

2.COMMENT: Clarify why there is a difference in building heights and square footage in the Development plan (Height35'5") and the Building Plan (Height 40',8")


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
09/13/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM02227-2239


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Kitchen exhaust to all apartment units shall exhaust to the outdoors sheet M4.6 (IMC2018,505.1) Complied
2. Approved/Subject to field approval

ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/21/2022 SHASEMA1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov