Permit Number: T22CM02230
Parcel: 140221130

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T22CM02230
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2022 DBENOIT1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change PLEASE CONTACT PC ADDRESSING BUILDING NUMBER NEEDS TO BE ASSIGNED PRIOR TO ISSUANCE Ph# 520-724-9512, EMAIL:ADDRESSING@PIMA.GOV
07/30/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02227, T22CM02228, T22CM02228, T22CM02230, T22CM02231, T22CM02232, T22CM02233, T22CM02234, T22CM02235, T22CM02236, T22CM02237, T22CM02238, T22CM02239

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. The allowable area increase calculations are still incorrect. The tabular values for At and NS being used are for type IV construction and not type VB construction. Please provide accurate allowable area increase calculations. Additionally, provide clarification as to why these calculations are being used as the current proposed building meets the minimum allowable area requirements per floor. The maximum allowable area (without frontage increases) per floor for an R-2, multi-story, protected with an NFPA 13 system is 21,000 sq. ft.. The plans state that each floor is 5,737-7,477 sq. ft. which is well below the maximum. Provide clarification or corrected calculations.
A meeting is suggested to resolve this final comment and approve the plans.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Kitchen exhaust to all apartment units shall exhaust to the outdoors sheet M4.6 (IMC2018,505.1) Complied
2. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved
Third Review:
1). OK
2). OK
3). OK
4). OK
5). OK-The total DFU load for all buildings is 3336 DFUs, the 8" sewer main on Utility plan pages 1.0 & 2.0 is undersized the sewer needs to be 10 or 12" depending on pitch. -IPC 710.1 **OK PER UTILITY SIZING METHOD PER ENGINEER RESPONSE**subject to field inspection**
6). OK
7).OK-Add Shower base or shower pan material specs to plan page P5.0 -IPC 106.3.1 , 421.5 **Plans Not specific subject to field inspection**


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/01/2022 PAUL CAMARENA ZONING REVIEW Reqs Change REVIEW TRANSMITTAL

FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM02227, T22CM02228, T22CM02229, T22CM02230, T22CM02231, T22CM02232, T22CM02233, T22CM02234, T22CM02235, T22CM02236 T22CM02237,T22CM02238, T22CM02239
Multi-Family (3rd Review)
1701 E VALENCIA RD Zoning C-2

TRANSMITTAL: August 1, 2022

1. Zoning has reviewed the building plans for compliance with the associated unapproved Development Package DP22-0029. Zoning cannot approve the building plans until the DP is approved.



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
08/01/2022 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/01/2022 PCAMARE1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.