Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM02210
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2022 | PCAMARE1 | OIP | REVIEW | Reqs Change | Transmittal Template FROM: Paul Camarena PDSD Residential Review Section PROJECT:T22CM02210 Roof top Solar Panels (1st Review) 2609 E PINAL VISTA TRANSMITTAL DATE: May 12, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. ? COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments. COMMENT: This plan set is not compliant with the Fire code. Demonstrate compliance with 2018 International Fire Code 1204.2.1.1. If the slope of the building is greater than 2:12 then compliance must be shown on the plans. Show a 36” wide access pathway from the eave to the ridge on both sides of the building. Relocate the solar panels to provide a clear fire pathway on each roof plane per 2018 IFC 1204.2.1.1 and 1204.2.1.2. ? COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.Camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/12/2022 | VVERA1 | OUT TO CUSTOMER | Completed |