Permit Number: T22CM02198
Parcel: 110140170

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T22CM02198
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM02198

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Conditionally Approved
1. The existing required fire rating between the units shall be maintained.
2. Fire blocking will be installed in all walls and concealed spaces (including the existing truss roof) where newly built or existing areas in which the framing is exposed during construction. 2018 IRC R302.11.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. All bath fans will be exhausted directly to the exterior. 2018 IRC M1505.2.
2. The kitchen exhaust hood shall be installed in accordance with the manufacture’s installation instructions and termination clearances.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
04/20/2022 NGARCIA3 OUT TO CUSTOMER Completed