05/31/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02192


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
THE RESPONSE TO THE FOLLOWING COMMENT SAYS: "SEE STRUCTURAL ENGINNER'S LETTER REGARDING THE ADEQUACY OF CURB....."
NO SUCH LETTER IS ATTACHED WITH THIS SUBMITTAL. PROVIDE LETTER.
1. Mechanical Drawing M2.1 shows new RTU-4 weighing 1200 pounds. Verify how it is supported and submit details and adequacy of Roof members supporting it as needed.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E2.1: Many of the Keynotes are not used or shown ie 2, 3, 5, 10, 11, 12, 16, 17, 18, 19, and 20 are not on the drawing.
Should add where required and call out the ones not used.


PLUMBING REVIEW COMMENTS:
Approved