| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/31/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM02192 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied THE RESPONSE TO THE FOLLOWING COMMENT SAYS: "SEE STRUCTURAL ENGINNER'S LETTER REGARDING THE ADEQUACY OF CURB....." NO SUCH LETTER IS ATTACHED WITH THIS SUBMITTAL. PROVIDE LETTER. 1. Mechanical Drawing M2.1 shows new RTU-4 weighing 1200 pounds. Verify how it is supported and submit details and adequacy of Roof members supporting it as needed. BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Conditionally Approved 1. Approved/Subject to field approval ELECTRICAL REVIEW COMMENTS Conditionally Approved E2.1: Many of the Keynotes are not used or shown ie 2, 3, 5, 10, 11, 12, 16, 17, 18, 19, and 20 are not on the drawing. Should add where required and call out the ones not used. PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |